NORTEC Raised Floor


Raised floor with highest demands to sustainability


TECHNICAL DATA

fibre-reinforced calcium sulphate panel, with galvanised steel sheet at bottom side on request, optionally with edge trim protection against damage and humidity

Panel thickness

30.5 – 44.5 mm

Dimensional deviation according to EN 12825

class 1

System weight

56 – 81 kg/m²

Standard pedestal heights

45 – 2,000 mm

Pedestal grid

600 x 600 mm

resistance to earth

≥ 1 x 106

ACOUSTICS

Normalised flanking level difference Dn,f,w

  • 47 – 64 dB*

Rated sound reduction index Rw

  • 61 dB

Reduction of impact sound pressure level ∆Lw

  • 11 – 36 dB*

Normalised flanking impact sound pressure level Ln,f,w

  • 73 – 38 dB*

*values depending on additional measures

 

25 – 2,000 mm

Pedestal Grid

600 x 600 mm

Resistance to Earth

  • ≥ 1 x 10⁶ (depending on covering)

 

FIRE PROTECTION

Reaction to fire performance of the carrier panel

  • A1 (non-combustible) according to EN 13501-1
  • A2 (non-combustible) according to DIN 4102-1

Fire resistance performance of the system

  • F 30 according to DIN 4102-2 as per AbP
  • REI 30 according to EN 13501-2 as per classification report

SUSTAINABILITY

Circular Economy

The product has a Cradle to Cradle Certified® certificat in “Gold”
CERTIFICATION: 5286
By implementing the Circular Economy ideology we avoid waste, toxic substances and environmental pollution. The panel is the basis for a closed cycle with separation and complete re-use of all materials.

Product highlights in the matter of sustainabilitY

with take-back guarantee carbon saving of 73 % compared with new product
extra credit points in terms of building certification (e. g. HQE)

Product self-declaration

A self-declaration can be generated according to the valid standards (ISO 14021).

The self-declaration provides extensive information about all environmental effects of the product. It can be used in the planning or tender phase to assess all sustainability-relevant aspects. It serves as a data basis for building certification systems such as LEED, DGNB and BREEAM.

EPD (Environmental Product Declaration)

A specific EPD for the product can be generated according to the valid standards. (EN 15804/ ISO 14025)

STATICS

Load and deflection class

1A (2 kN) – 5A (5 kN) according to EN 12825

Safety factor

2

Tested Seismic safety

possible in A – F according to IBC (International Building Code)/AC 156

NORTEC power
Raised Floor for heavy-duty areas


TECHNICAL DATA

Panel

fibre-reinforced calcium sulphate panel, optionally with galvanised steel sheet at bottom side on request surrounding edge trim protection against damage and humidity on request.

Panel thickness

16- 38.5 mm

Dimensional deviation

class 1 in acc with EN 12825

System weight

32 – 62 kg/m²

Standard pedestal heights

25 – 2,000 mm

Pedestal Grid

600 x 600 mm

Resistance to Earth

  • ≥ 1 x 10⁶ (depending on covering)

 

ACOUSTICS

Normalised flanking level difference DN,F,W

  • 49 dB

Rated sound reduction index Rw

  • 61 dB

Reduction of impact sound pressure level ∆Lw

  • 14 dB

Normalised flanking impact sound pressure level LN,F,W

  • 70 dB

FIRE PROTECTION

Reaction to fire performance of the carrier panel according to DIN 4102-1

  • A2 (non-combustible)

Reaction to fire performance of the carrier panel according to EN 13501-1

  • A1 (non-combustible)

Fire resistance performance of the system according to DIN 4102-2

  • F30

Fire resistance performance of the system according to DIN 13501-2

  • REI 30

SUSTAINABILITY

Circular Economy

By implementing the Circular Economy ideology we avoid waste, toxic substances and environmental pollution. The aim is to achieve a technical cycle, which ensures the separation and the complete re-use of all materials.

Product self-declaration

The self-declaration provides extensive information about all environmental effects of the product. It can be used in the planning or tender phase to assess all sustainability-relevant aspects. It serves as a data basis for building certification systems such as LEED, DGNB, BNB and BREEAM.

EPD (Environmental Product Declaration)

A specific EPD for the product can be generated according to the valid standards. (EN 15804/ ISO 14025)

STATICS

Seismic safety

International Building Code (IBC)
Possible in A – F

Load and deflection class

according to EN 12825
6A (6-15 kN)

Safety factor

2