NORTEC Raised Floor
Raised floor with highest demands to sustainability
TECHNICAL DATA
fibre-reinforced calcium sulphate panel, with galvanised steel sheet at bottom side on request, optionally with edge trim protection against damage and humidity
Panel thickness
30.5 – 44.5 mm
Dimensional deviation according to EN 12825
class 1
System weight
56 – 81 kg/m²
Standard pedestal heights
45 – 2,000 mm
Pedestal grid
600 x 600 mm
resistance to earth
≥ 1 x 106 Ω
ACOUSTICS
Normalised flanking level difference Dn,f,w
- 47 – 64 dB*
Rated sound reduction index Rw
- 61 dB
Reduction of impact sound pressure level ∆Lw
- 11 – 36 dB*
Normalised flanking impact sound pressure level Ln,f,w
- 73 – 38 dB*
*values depending on additional measures
25 – 2,000 mm
Pedestal Grid
600 x 600 mm
Resistance to Earth
- ≥ 1 x 10⁶ (depending on covering)
FIRE PROTECTION
Reaction to fire performance of the carrier panel
- A1 (non-combustible) according to EN 13501-1
- A2 (non-combustible) according to DIN 4102-1
Fire resistance performance of the system
- F 30 according to DIN 4102-2 as per AbP
- REI 30 according to EN 13501-2 as per classification report
SUSTAINABILITY
Circular Economy
The product has a Cradle to Cradle Certified® certificat in “Gold”
CERTIFICATION: 5286
By implementing the Circular Economy ideology we avoid waste, toxic substances and environmental pollution. The panel is the basis for a closed cycle with separation and complete re-use of all materials.
Product highlights in the matter of sustainabilitY
with take-back guarantee carbon saving of 73 % compared with new product
extra credit points in terms of building certification (e. g. HQE)
Product self-declaration
A self-declaration can be generated according to the valid standards (ISO 14021).
The self-declaration provides extensive information about all environmental effects of the product. It can be used in the planning or tender phase to assess all sustainability-relevant aspects. It serves as a data basis for building certification systems such as LEED, DGNB and BREEAM.
EPD (Environmental Product Declaration)
A specific EPD for the product can be generated according to the valid standards. (EN 15804/ ISO 14025)
STATICS
Load and deflection class
1A (2 kN) – 5A (5 kN) according to EN 12825
Safety factor
2
Tested Seismic safety
possible in A – F according to IBC (International Building Code)/AC 156
NORTEC power
Raised Floor for heavy-duty areas
TECHNICAL DATA
Panel
fibre-reinforced calcium sulphate panel, optionally with galvanised steel sheet at bottom side on request surrounding edge trim protection against damage and humidity on request.
Panel thickness
16- 38.5 mm
Dimensional deviation
class 1 in acc with EN 12825
System weight
32 – 62 kg/m²
Standard pedestal heights
25 – 2,000 mm
Pedestal Grid
600 x 600 mm
Resistance to Earth
- ≥ 1 x 10⁶ (depending on covering)
ACOUSTICS
Normalised flanking level difference DN,F,W
- 49 dB
Rated sound reduction index Rw
- 61 dB
Reduction of impact sound pressure level ∆Lw
- 14 dB
Normalised flanking impact sound pressure level LN,F,W
- 70 dB
FIRE PROTECTION
Reaction to fire performance of the carrier panel according to DIN 4102-1
- A2 (non-combustible)
Reaction to fire performance of the carrier panel according to EN 13501-1
- A1 (non-combustible)
Fire resistance performance of the system according to DIN 4102-2
- F30
Fire resistance performance of the system according to DIN 13501-2
- REI 30
SUSTAINABILITY
Circular Economy
By implementing the Circular Economy ideology we avoid waste, toxic substances and environmental pollution. The aim is to achieve a technical cycle, which ensures the separation and the complete re-use of all materials.
Product self-declaration
The self-declaration provides extensive information about all environmental effects of the product. It can be used in the planning or tender phase to assess all sustainability-relevant aspects. It serves as a data basis for building certification systems such as LEED, DGNB, BNB and BREEAM.
EPD (Environmental Product Declaration)
A specific EPD for the product can be generated according to the valid standards. (EN 15804/ ISO 14025)
STATICS
Seismic safety
International Building Code (IBC)
Possible in A – F
Load and deflection class
according to EN 12825
6A (6-15 kN)
Safety factor
2